Visitor conference rooms are a high-visibility
location for displaying LED lighting to our guests. To demonstrate
the variety of available LED lighting products, we did not use
the same fixtures in all visitor conference rooms. We chose fixtures
from several different vendors, which allowed us to learn more
about LED lighting solutions.
These new LED lighting solutions generally
achieved average energy savings from 25 to 63 percent for each
room, compared to the non-LED fixtures they replaced.
Potential cost savings are increased by the
lower maintenance and disposal costs made possible by the long
service life of LEDs (targeted at 50,000 hours) and by the fact
that they do not contain mercury or other hazardous materials requiring
specialized disposal.
Note: In Room #1, we converted standard fluorescent
troffers and CFL can lights to Cree-designed specialized color-mixing
troffers and Renaissance Lighting LED recessed can lights. The
color-mixing troffers create spectacular lighting effects because
they can reproduce the full spectrum of visible colors. These color-mixing
fixtures are not commercially available, however, and are not detailed
below.
| Location |
Before
Conversion |
After
Conversion |
Average
Savings |
| Room #2 |
6 fluorescent troffers with three T8 tubes each
using 91 W
4 CFL can lights each using 52 W |
12 Wissen-LUX troffers each using 61 W
4 Cree LED Lighting Solutions, Inc. can lights each using 12
W |
45%* |
| |
|
|
|
| Room #3 |
6 fluorescent troffers with three T8 tubes each
using 91 W
4 CFL can lights each using 52 W |
6 LED Dynamics, Inc. troffers with three T8
tubes each using 74 W
4 Renaissance Lighting can lights each using 41 W / 15 W |
26% / 40%** |
| |
|
|
|
| Room #4 |
10 fluorescent troffers (three T8 tubes) each
using 91 W
8 CFL can lights each using 52 W |
10 LED Lighting Fixtures, Inc. troffers (prototypes)
each using 75 W
8 Cree LED Lighting Solutions, Inc. can lights each using 12
W |
63%*** |
| |
|
|
|
| Room #5 |
8 fluorescent troffers (three T8 tubes) each
using 91 W
8 CFL can lights each using 52 W |
8 AlbEO Technologies, Inc. troffers each using
66 W
8 Renaissance Lighting can lights each using 41 W / 15 W |
25% / 44%** |
| |
|
|
|
| Room #6 |
8 fluorescent troffers (three T8 tubes) each
using 91 W
8 CFL can lights each using 52 W |
8 Wissen-LUX troffers each using 61 W
8 Renaissance Lighting can lights each using 41 W / 15 W |
29% / 47%** |
* We replaced the six original 2x4 fluorescent
troffers with 12 Wissen-LUX 2x2 troffers, but only six Wissen-LUX
troffers were required to match the foot-candle-level of the original
fluorescent fixtures. The savings calculations are based on using
just six LED troffers.
** Renaissance Lighting’s EVO can lights
can operate at multiple light levels. Their energy-demands range
from 41 to 15 W. The savings calculations are based on both these
high and low levels.
*** We replaced 10 of the original 2x4 fluorescent
troffers, but only five LED Lighting Fixtures, Inc. 2x2 troffers
were required to match the foot-candle-level of the fluorescent
fixtures. The savings calculations are based on using just five
LED troffers.
AlbEO Technologies, Inc.
3125 Sterling Circle, Unit 105
Boulder, CO 80301
www.albeotech.com
LED Dynamics, Inc.
44 Hull Street
Randolph, VT 05060
www.leddynamics.com
Cree LED Lighting Solutions, Inc.
617 Davis Drive, Suite 100
Morrisville, NC 27560
www.creells.com
Renaissance Lighting
480 Springpark Place, Suite 900
Herndon, VA 20170
www.rllight.com
Wissen Lux S.p.A.
Via Lombardi 19/18
20152
Milan, Italy
www.wissenlux.com
|